Thermal safety valve
VST200
- Excellent safety for solid fuel boilers.
- Two independant temperature sensors.
- Metal hose coating of the capillary tubes.
The series VST200 prevents excess temperatures in solid fuel fired boilers. Heating capacities of up to a maximum of 100 kW are allowed for these systems. The thermal safety valve is a pressure-relieved single-seated valve that opens in case of escalating temperature. Install the thermal safety valve preferably in the cold water inlet of the safety heat exchanger.
Product range
VST212, Internal thread
| Art.no. | Reference | DN | Opening temperature [⁰C] | Relief capacity [m³/h] | Connection A | Connection B | C [mm] | D [mm] | E [mm] | F [mm] | Weight [kg] |
| 36028000 | VST212 | 20 | 95 ± 3 | 1,35 | G ¾" | G ½" | 60 | 34,5 | 67,1 | 157,5 | 0,65 |
Installation support
Installation examples
Documents
| Name | Download |
| Installation instruction VST200 |
|
Technical data
Technical data
| Pressure class: | PN 10 |
| Boiler heat capacity, max.: | 100 kW |
| Length of capillary tube: | 1,3 m |
| Temperature - sensor, max.: | +125 °C |
| Opening temperature - sensor: | 95°C ± 3°C |
| Connections, Valve: | Internal thread (G), ISO 228/1 |
| Connections, Immersion pocket: | External thread (G), ISO 228/1 |
| Material, Valve housing and other metal parts with fluid contact: | Brass, CW 617N - DIN 12164/5 |
Acc. to standard EN 14597-2, VdTÜV-Merkblatt
Download area
Download area
| Type | Preview | Download |
| Data Sheet | VST200 |
|
| Installation instruction | VST200 |
|
| Certificate | Declaration of Conformity, VST200 |
|
| Certificate | Building Product Declaration BPD3, VST200 |
|
| Image | VST212, high res |
|
| 2D Image | VST200 |
|
| 2D Image | Immersion pocket |
|
| 3D drawing (stp file) | VST212, DN20 |
|
Quick links