LVD 2014/35/EU
EMC 2014/30/EU
RoHS 2011/65/EU
CCW=Counter clockwise working direction
CW= Clockwise working direction
ARC368/ARC369 (Proportional)
Auxiliary switch settings ARC368 - S1
S1 and S2 auxiliary switches are independent from each other and can be set individually. Auxiliary switch S1 is set by moving the inner circle to the desirable position, when the inner arrow points on the upper semicircle wire 1 is connected to wire 2, and when the inner arrow points on the lower semicircle wire 1 is connected to wire 3. Auxiliary switch S2 is set by moving the outer circle to the desirable position, when the outer arrow points on the upper semicircle wire 4 is connected to wire 5, and when the outer arrow points on the lower semicircle wire 4 is connected to wire 6.
The inner and outer circle rotates 180º counter clock wise (CCW) when the actuator moves 90º clock wise (CW) and vice versa.